Transient comparison relay based on super-imposed component for the protection of transformer feeder circuits

Ping Ye,Shenxing Shi,H. Tony Yip,Zhiqian Bo,Ben R J Caunce,Xinzhou Dong
2002-01-01
Abstract:This paper presents a new technique for transformer feeder protection, based on the detection of fault generated super-imposed current signals both on the feeder and inside the transformer. The proposed relay units are connected to the current transformers at both ends of the transformer-feeder circuit and the earth of the star winding of the transformer, and are responsible for capturing the fault generated super-imposed signals. The polarities of the signals at both ends of the protected section are then compared, from which whether a fault is within the protected zone can be derived. A 132/22 kV power transformer connected to a feeder system is simulated using the Real Time Digital Simulator (RTDS). The responses are examined for a number of practically encountered different system and fault conditions. Results show that the proposed technique can correctly distinguish between internal and external faults. The technique is not only simple in application and fast in operation, but also only require current transducers and can be applied to places where VTs are not available.