Integrated Protection of Transmission Network Using a New Directional Approach

Bo, Z.Q.,Dong, X.Z.,Caunce, B.R.J.,Yang, Y.M.
DOI: https://doi.org/10.1049/cp:20030677
2003-01-01
Abstract:This paper presents a novel protection and control scheme for transmission networks, the transient polarity directional comparison scheme. The technique is based on the detection and processing of fault generated transient current signals, in which specially designed protection relays are installed at each substation of a transmission network. The transient detection unit of the relay detects the faulted generated super-imposed current signals. The transient polarity identification algorithm is then applied to the superimposed signals to identify the polarity of the signal detected. The direction of a fault is determined by comparison of the polarity of the signals derived from all the line sections connected to the station. The actual faulted section is identified by processing the directional information from various stations. Simulation results presented in the paper demonstrate the feasibility of the scheme.
What problem does this paper attempt to address?