A field scheme of feeder automation system based on non-communication protection

SHI Shen-xing,XU Gang,DONG Xin-zhou,YIN Di-qing,LIU Kun,WANG Kai
DOI: https://doi.org/10.3969/j.issn.1003-3076.2013.01.021
2013-01-01
Abstract:Non-communication protection of feeders can quickly and selectively isolate the asymmetrical fault and recover power supply to the sound feeder sections.But how to coordinate with the protection of transformer and to cope with symmetrical fault need to be solved when applied into the field.This paper proposes a field scheme which can meet the requirements of coordinating with the protection of transformer and quickly isolating the symmetrical fault.The scheme presented in the paper configured the non-communciation protection feeders according to the time requirements of the transformer's protection,and tripped the symmertical fault instantly and without selectivity based on three phases voltages,and then used the re-closure technology intergrated in the relay to determine the fault section and to recover the power supply to the healthy feeder sections.The field scheme can achieve isolating the fault in the feeder and recovering the power supply to the load fast without the need of communication channel.