NON-COMMUNICATION PROTECTION FOR DISTRIBUTION SYSTEMS WITH THE TAPPED-LOAD

刘建凯,董新洲,薄志谦
DOI: https://doi.org/10.3321/j.issn:1000-1026.2003.01.009
2003-01-01
Abstract:This paper presents a new scheme for non-communication protection of distribution systems with the tapped-load, which is based on the research pronounced before on the non-communication protection of the systems without the tapped-load. In distribution systems, the current value of the faulted phase will increase significantly after the fault occurs. And the current value of the healthy phase will chop suddenly after one breaker of the faulted line opens. Furthermore, the changes are related with the breaker operating time. Based on the phenomena, the algorithm is derived to accelerate the operation of the relays in succession immediately after one breaker of the protected line opens firstly. As a result, the fault is isolated rapidly. Theory analysis and simulation studies show that the new scheme has some advantages, such as high-speed operation, reliability, adaptability and so on. And it can be applied to deal with the asymmetry fault occurring in the systems.
What problem does this paper attempt to address?