Distribution Line Automation System Based on Non-Communication Protection in the Case of Symmetrical Fault

刘琨,董新洲,施慎行,王宾
DOI: https://doi.org/10.1109/apap.2011.6180481
2011-01-01
Abstract:Distribution line non-communication protection (DNCP) can quickly and selectively isolate unsymmetrical faults, but the performance of the distribution line automation system is not satisfactory with symmetrical faults. This paper presents a scheme which can quickly isolate symmetrical faults and block the operation of the reserve power source automatic connection device (BZT). The DNCP which is closed to the source operates instantaneously to avoid overheating of the electrical equipment. When the voltage magnitude falls, the BZT will detect the negative voltage two cycles earlier to make a decision to avoid connecting to a permanent fault and tripping again for the ring main unit. Electro magnetic transient program (EMTP) simulations show the effectiveness of the scheme.