Novel Connection Scheme of Backup Power Supply Adaptive to Distribution Line Non-Communication Protection and New Criterion for High Voltage and Large Capacity Induction Motor

Kun Liu,Xinzhou Dong,Zhiqian Bo
DOI: https://doi.org/10.1109/appeec.2009.4918525
2009-01-01
Abstract:This paper presents a new practical backup power supply connection scheme for distribution line non-communication protection (DNCP). Simulation tests have been conducted using the alternate transient program (ATP) with respect to a typical single circuit breaker multi-section system. The results prove that the new scheme is able to not only recover the power supply of loads on healthy lines automatically, but also create disturbances in favor of accelerated over current (AOC) criterion. Aiming at the failure of directional under voltage (DUV) criterion derived from high voltage and large capacity induction motor load, a novel criterion using the increment of reactive power is proposed.