SENSITIVE INSULATOR METHOD-A NEW METHOD TO DETECT THE FAULTY INSULATOR

安玲,江秀臣,朱宇,韩振东,陈亚珠,程剑
DOI: https://doi.org/10.3321/j.issn:0258-8013.2002.09.023
2002-01-01
Abstract:A new method called sensitive insulator method is introduced in detail, which is developed on the basis of the distribution voltage method. If there is a faulty insulator in the strings, not only its own distribution voltage but also the other insulators?will change to some degree, among which, insulators which are more sensitive to different location are called sensitive insulators. It is proved that the forth insulator near the earth terminal is the most sensitive insulator to the faulty degree, no matter where the faulty insulator locates in the strings. Therefore measuring this insulator only can determine whether there is a faulty insulator or not. By this method, the workload can be decreased greatly.
What problem does this paper attempt to address?