Abstract:Failed fitting samples of a 500 kV electric power transmission line was investigated by means of mechanical property test, electrochemical test, as well as SEM and XRD characterization. The results show that sulfur is the critical factor of fittings corrosion. It forms soluble sulfate to consume zinc coatings faster. Furthermore, tensile stress and fretting corrosion also affect the fittings corrosion. The conclusions coincide fairly well with the service situations of fittings in terms of acid rain and corrosion in the relevant areas of Guangxi and Hunan province. Then anti- corrosion measures for fittings in industrial areas are proposed.