Transmission of vibration of a power transformer from the internal structures to the tank

Ming Jin,Jie Pan,Hai Huang,Jianping Zhou
2012-01-01
Abstract:Vibration-based transformer condition monitoring aims to identify the conditions of a transformer's internal structures, such as its windings and core, by measuring the vibration of the transformer tank. The correlation between the vibration signals from the internal structures and those from the transformer tank is dependent on the characteristics of the transmission path between them. Such vibration transmission is determined by direct mechanical coupling between the internal structures and the tank, and by indirect coupling through the fluid-structure interaction. This paper examines the vibration transmission characteristics based on experimental work on a 110kV power transformer. A series of dynamic and electrical tests were conducted on the power transformer with and without transformer cooling oil. Both internal and tank vibration were measured simultaneously. The effects of the transformer cooling oil on the vibration transmission are discussed. Finally, optimal locations on the tank for vibration measurement and monitoring of the transformer internal structures are presented.