Abstract:The research object is two-stage compression heat pump with economizer. The representative working refrigerants of the theoretical analysis are HFC152a and HFC245fa. The advantages and the optimal intermediate pressure of two-stage compression heat pump with economizer were investigated by theoretical methodology. The results showed that, in moderately high temperature heat pump situation, the system of two-stage compression heat pump with economizer is much more advantaged than conventional single-stage compression heat pump. When the evaporating temperature is 55°C and the condensing temperature is 100°C, the heating COPh of two-stage compression heat pump with economizer at optimal intermediate pressure are 15.2% with HFC152a, and 12.4% with HFC245fa larger than that of the conventional single-stage compression heat pump system. The lower discharging temperature is another advantage of two-stage compression heat pump with economizer.