Research on a new two-stage compression for heat pump air-conditioning with R32

Zhang Qian,Yan Gang,Bai Tao
DOI: https://doi.org/10.3969/j.issn.1001-7100.2011.02.008
2011-01-01
Abstract:In our study,because the high exhaust temperature was occured in single-stage compression for air-conditioning with R32,a two-stage compression refrigeration cycle using a twin-cylinder rotary compressor was adopted in air-conditioning to reduce the pressure ratio and exhaust temperature,and enchance coefficient of performance(CCOP).A theoretical model about two-stage compression cycle with R32 was established,and performance parameters were calculated in cooling mood and heating mood.Results show that exhaust temperature of the compressor was reduced respectively by 30.1℃ in cooling mood and 28.5℃ in heating mood,CCOP was improved respectively by 3.02% and 8.15% for two-stage compression cycle.The impact of intermediate temperature on the compression ratio,exhaust temperature and CCOP was analyzed,and the best intermediate temperature was given.
What problem does this paper attempt to address?