Research on Audible Noise and Radio Interference Characteristics of Aged 500 kV Shunde-Jiangmen Transmission Line

范亚洲,汤振鹏,陈澜,陈剑平,卞星明,王黎明
DOI: https://doi.org/10.13296/j.1001-1609.hva.2013.02.002
2013-01-01
Abstract:The electromagnetic environment problem,which caused by corona discharge in transmission lines is one of UHV construction difficulty.The audible noise(AN)and radio interference(RI)are important indexes of the corona discharge characteristics,the AN and RI would be changed with the operation time is go on and the atmospheric environment variation.The LGJ400/50 conductor of Shunde-Jiangming,which had been used in South Guangdong Province over 16 years and the new same conductor were used as the test simple with a effective and convenience corona cage in this paper to research the AN and RI feature,while the Scanning Electron Microscope and Phase Shift MicroXAM-3D were used to detect the surface condition of the new and aged conductor.The sound meter and radio interference receiver were taken to detect the corona phenomenon,and the detected values were compared.The experiment results illustrated that the surface conductor of aged conductor worse than new ones,and the composition of the aged conductor surface substance was more complex;the AN value of aged conductor was higher than new ones about 1~5 dB(A);the RI value of the aged conductor was higher than new ones no more than 10 dB.The results may supplied design and maintain suggestions to relevant department.