Variation of Corona Effects for Long-term Operated Conductors in AC Power Transmission Lines
BIAN Xingming,CHEN Fangdong,CHEN Lan,WAN Shuwei,WANG Liming,GUAN Zhicheng
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.030
2013-01-01
Abstract:Corona effects and its related electromagnetic environment on AC long-term operated conductors are important problems to be resolved for transmission lines.However,the conclusions obtained from earlier domestic and overseas works cannot well reflect the surface conditions and corona discharge effects of long-term operated conductors.In order to investigate the relation between surface conditions and corona effects for long-term operated conductors,we measured the surface conditions and roughness degree of the AC 500 kV conductor samples from areas near Beijing,Wuhan,and Guangzhou,and analyzed the variation of the surface conditions for the long-term operated conductors.The roughness degree may increase in the area where the relative humidity,temperature,and contamination in the environment are relatively high and close to the sea.According to corona tests in a corona cage on a simulative overhead line,it is found that the corona discharge intensity for long-term operated conductors is much stronger than that for new ones;hence,the corona inception voltages for aged conductors are lower while the audible noise and radio noise are higher than those of the new ones.In circumstances with better nature conditions,the surface roughness degree of short-term operated conductor can be less than that of new ones,hence,the corona discharge on the conductor is improved,which is in accordance with the earlier conclusions abroad.