Corona Initial Voltage Change Feature for Aged Conductor of 500 kV Shunjiang-Jiangmen

汤振鹏,陈剑平,陈澜,范亚洲,曾伟灵,王黎明
DOI: https://doi.org/10.13296/j.1001-1609.hva.2013.01.024
2013-01-01
Abstract:The electromagnetic environment problem,which caused by corona discharge in transmission lines is one of UHV construction difficulty.The corona inception voltage(ICV) is an important index of the corona discharge characteristics,the ICV would be changed with the operation time is go on and the atmospheric environment very.This LGJ400/50 conductor of Shunde-Jiangming,which had been used in South Guangdong Province over 16 years,was sit as the test simple with a effective and convenience corona cage in this paper to research the ICV feature.An ultraviolet imager was used to detect the photon count number caused by corona discharge of the single new and aged LGJ400/50 then the ICV value was calculated.The experiment results showed that ICV value of the aged LGJ400/50 was 115.8 kV while the new ones was 129.1 kV.Then the results were compared with the value which calculated by Peek low with the model of smooth cylinder conductor,the roughness coefficient m of the new and aged LGJ400/50 were gained,the value drop from 0.85 to 0.77,respectively for new and aged ones.The results demonstrated that the ICV of aged conductor dropped obvious,the conclusion will provide design and maintain suggestions for related department.