Calculation of Loss Factors for Metal Sheath and Armour of HV Cables

LIU Ying
DOI: https://doi.org/10.3969/j.issn.1672-6901.2013.02.001
2013-01-01
Abstract:When determining the nominal current rating of power cables,loss factors of metal layers such as the sheath and armour must be calculated accurately,especially for high-voltage single-core cables whose metal layers are collected and grounded directly at both sides of the cable line.Some calculation methods for loss factors of cables in simple symmetric configurations such as those in flat or trefoil arrangements are recommended by IEC 60287.For more complex cable structures and complicated practical arrangements,an equivalent circuit should be established and an equation set be created whose solutions are circulating currents in the metal layers such as sheath,strengthen and armour,and accordingly loss factors can be obtained.Selection between these two methods is condition-based.
What problem does this paper attempt to address?