Thermal Resistance Properties of the Part between Metal Sheath and Conductor in High-voltage Power Cable

Jian-kang ZHAO,You-hing FAN,Xiao-bing WANG,Sheng-tao LI,Hai-qing NIU
DOI: https://doi.org/10.13336/j.1003-6520.hve.2008.11.027
2008-01-01
Abstract:To appropriately apply the IEC 60287 standard to both the on-line temperature monitoring and current rating calculations in power cable lines, the current rating experiments were performed on one single-conductor high voltage power cable, from which not only the temperature distribution but also the thermal resistance of each layer were obtained according to the thermal conduction model provided by IEC 60287. Then, the experimental values of thermal resistance were compared to the theoretical ones obtained directly from IEC 60287 standard. The results show that the experimental value of thermal resistance of the part between metal sheath and conductor is much different from the theoretical prediction by 56.8%, which is attributed to the gas gaps among waterstop, metal sheath and conductor. Therefore, according to the specific structure of power cable, an improved method to calculate the thermal resistance between metal sheath and conductor in the cable was proposed on the basis of IEC 60287, in which the part between metal sheath and conductor is treated as two layers with different thermal resistance. In addition, according to the experimental values of thermal resistance, the modified thermal resistance coefficient of the part between metal sheath and conductor is estimated as 20.0 Km/W, which is far more than the standard value of 6.0 Km/W.