Research and Simulation of Capacitance Current Compensating Countermeasure for Phase Differential Protection of 750 kV Transmission Lines

MIAO Shi-hong,LIU Pei,CHENG Shi-jie,MENG Luo-fei
2008-01-01
Abstract:The authors study the development situation of 750KV transmission line relay protection home and abroad.According to the concrete parameters of 750kV transmission lines in Northwest China power grid, the EMTP model of 750kV transmission line is built by which the simulation of special problems of 750kV transmission line and that of various fault conditions under different system operation modes are carried out.The operation characteristics and effects of common phasor differential protection, fault component differential protection and zero-sequence differential protection are discoursed upon while various compensation measures have been adopted, and comparative analysis on operation characteristics of differential protections for 750kV transmission line and 500kV transmission line is conducted.Simulation results show that as for long distance EHV transmission line in Northwest China power grid, the differential protection combining common phasor differential protection with capacitance current compensation with fault component differential protection should applied, and zero-sequence differential protection is used as auxiliary protection.
What problem does this paper attempt to address?