Study on Shielding Failure Flashover Rate for Transmission Lines Based on Exposure Arc-projection Model

马凌,文远芳,陈敏,黄韬,李健
2010-01-01
Abstract:The exposure distance model based EGM is used widely in calculation of engineering lightning protection.However,this model cannot explain the phenomenon of shielding failure when the protect angle is negative for laying ground wire.Considering the influence of ground obliquity and lightning incidence angle,new formulas of the maximum striking distance and the exposure arc projection length are deduced with the coordinate geometry of transmission lines.The calculation method of shielding failure based exposure arc projection model is established and the lightning withstand level of transmission lines is calculated at the conditions of the typical voltage class.It also discusses the influence of striking distance coefficient,the protect angle and the ground obliquity on SFFOR.The calculation results show that the exposure distance model and the exposure arc projection model can both calculate the SFFOR of transmission lines.In addition,the exposure arc projection model explains why the shielding failure phenomenon still exists when the protect angle is negative.The exposure arc projection model is an advanced method and worth popularization and application.
What problem does this paper attempt to address?