Test on Power Frequency Flashover Property of 110kv Single and Double Composite Insulator Strings

马奎,李刚,杨文华,马波
DOI: https://doi.org/10.3969/j.issn.1672-3643.2011.06.008
2011-01-01
Abstract:110 kV long rod composit insulators with singel string or different suspended double strings were made dry and wet power frequency flashover voltage test and the test after hydrophobicity lost,analyzes the cause of wet flashover voltage decreasing remarkably for the double string composite insulators after the hydrophobicity lost,suggests using inverse V type strings improve double strings composite insulators.
What problem does this paper attempt to address?