Research on Pollution Flashover Performance of ±1100kV Long Line Disc Insulator String

YU Xinzhe,ZHOU Jun,LIU Bo,WU Haozhe,XU Yueneng,ZHANG Qiaogen
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.2189
2018-01-01
Abstract:UHVDC transmission technology can satisfy long-distance,large-capacity and high-efficiency energy allocation.Compared with ±800kV line,transmission efficiency and distance of ±1100kV is further enhanced with significant economic and social benefits.Head size of±1100kV line tower is affected by insulator string length determined by artificial pollution test of long insulator string.In order to ensure safety and economy of ±1100kV UHVDC project,artificial pollution test should be carried out under conditions of full ±1100kV voltage,full size and different parallel string distance to obtain pollution flashover characteristics.UHVDC ± 1400kV/2A test capacity in UHVDC test base has solved voltage stability problems within the maximum output voltage and under high current load.Meanwhile,test fog uniformity control issue of extra long size test sample has also been cleared out.These two key technologies make ± 1100kV level full-voltage full-size test possible in practice.Based on that,in this paper,a series of DC flashover tests were carried out,including long string tests up to 15.6m,full voltage tests up to DC 1100kV,parallel string test from 500 to 1000 mm spacing and up to 6 parallel insulator strings.Relations between insulator string length,parallel string distance,string type and pollution flashover voltage were obtained with long string test under full ±1100kV voltage.Test results showed that string length and pollution flashover voltage presented a linear relationship within ±ll00kV.When double parallel string or multi-parallel string are adopted in ±1100kV project,the distance between string centers should be greater than 600mm to avoid interaction between adjacent strings.String length correction of multi-parallel string should be considered in long span transmission tower design.According to probability analysis,the correction factor was calculated under various conditions.In this paper,based on up-and-down method,relation between insulator length and pollution flashover voltage of ±1100kV long string was obtained within full voltage.Influence of parallel insulator string distances on pollution flashover voltage was investigated.Outdoor insulator design of multi-parallel insulator string was also analyzed.These results can be directly adopted in outdoor insulator design of±1100kV transmission line.
What problem does this paper attempt to address?