Practical Harmonic Detection Methods with Separate Frequency
夏向阳,罗安
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.06.036
2007-01-01
Abstract:The wide use of nonlinear loads causes significant power quality degradation in power distribution networks in terms of current/voltage harmonics,power factor and resonance problems.Harmonics can be limited either by improving the design of nonlinear loads(e.g.,increasing the number of pulses,enlarging the ac choke inductance,considering active front-ends,etc)or by adding filters to the power system.The accuracy and the speed of dynamic response for harmonic detection affect the performance of active power filters greatly.Because the ip-iq method based on instantaneous reactive power can not extract single harmonic component,the improved harmonic detection method with separate frequency is adopted,it separates single current into active and reactive current in a-b-c three-phase coordinate using the ip-iq method,and it uses low-pass filter to get sinusoidal or harmonic of active current and reactive current,in which three-phase to two-phase coordinate transformation and inverse transformation are ignored,thereby,the method can better detect three-phase sinusoidal and harmonic current.