Numerical Simulation Study on the Smoke Blockage Effect of Air Curtains in a Real Subway Station

Zhen-kun WU,He-ping ZHANG,Ye-hua SHENG,Zhen CHEN,Hao HU,Bin YAO
DOI: https://doi.org/10.3969/j.issn.1004-5309.2013.01.05
2013-01-01
Fire Safety Science
Abstract:The smoke will flow into stairwell when there is fire in platform floor.In order to study the smoke blockage effect of air curtain exit jet.The author studied it by numerical simulation.Main research is on the velocities and angles of air curtain exit jet.The velocities were set as 3m/s,4m/s,5m/s and 10m/s.The angles were set as 0°,15°and 30°.By comparative of temperature front and back of air curtain exit jet.It was found that when the velocity was 4m/s or 5m/s can obstruct the smoke very well.The angle of 15° is better than 0°and 30°for the block off smoke.