Experimental study on ecological characteristic of legionella in cooling tower water

Lin Hai-jiang,Jiang Wei-li,Guo Yi-fang,Chen Yue,Xu Biao,Wang Wei-bing
DOI: https://doi.org/10.3969/j.issn.1004-8685.2007.08.019
2007-01-01
Abstract:Objective:To learn the ecologic characters of Legionella in cooling tower water of central air-conditioning system,and provide evidence and information for Legionella disinfection.Methods:Experimental study on ecological characteristic of Legionella in cooling tower water was carried out through the methods of routine culture.Results:The quantity of Legionella in experimental simulation water has a significant association with water temperature.The quantity of Legionella reached its peak when the water temperature got to about 35℃.However,Legionella could not be detected when the temperature dropped below 20℃,but it could be detected in bio-film.Conclusion:The growth of Legionella in experimental simulation water has clear relationship with water temperature and biofilm provide safe-room for Legionella to live through.
What problem does this paper attempt to address?