Experimental study on transmitting mechanism of Legionella in cooling tower water of central air-conditioning system

Lin Hai-jiang,Jiang Wei-li,Qiu Dan-hong,Chen Yue,Wang Wei-bing
DOI: https://doi.org/10.3969/j.issn.1004-8685.2007.12.076
2007-01-01
Abstract:Objective:To learn the transmit mechanism of Legionella in cooling tower water infecting population.Methods:Experimental study on Legionella in air 20 cm above the cooling tower of central air-conditioning system was carried out through the methods of routine culture.Results:Legionella in air 20 cm above the cooling tower can be detected from June to September.1 CFU(Colony-forming unit) in June,5 CFU in July,6 CFU in August and 1 CFU in September respectively.However,Legionella in air 20 cm above the cooling tower cannot be detected in other months.Conclusion:Aerosol of Legionella exists in air 20cm above the cooling tower.It may be the transmitting mechanism of Legionella in cooling tower water infecting population and pose great threat to public health.
What problem does this paper attempt to address?