Contamination of Legionella spp.in Water Distribution Systems in 8 Hospitals of Shanghai,China

TAO Li-li,HU Bi-jie,ZHOU Zhao-yan,YU Ling-ling,GAO Xiao-dong,ZHOU Chun-mei,BAO Rong
2010-01-01
Abstract:OBJECTIVE To investigate the contamination of legionella spp.in hospital water distribution systems,and analyse the associated risk factors.METHODS 193 water samples were collected from the distribution systems of 8 hospitals in Shanghai and the water samples were cultured for legionellaspp.and amoeba,latex agglutination test were used to identify the serogroups of legionella that have been isolated.Meanwhile,the associated factors of legion Ella contamination were collected.RESULTS Among the 8 sampling hospitals,7(87.5%) were contaminated by legionella spp.2 hospitals were detected with high level contamination(>30%) of legionella pneumophila.In 193 water samples that have been collected,83(43.0%) were positive for legionella spp,including 33 for legionella pneumophila.Among the positive samples,as many as 63 samples had the concentration≥103 cfu/L.In the risk factors analysis for legion Ella contamination,the contamination of amoeba,lack of distribution system disinfection,use of galvanized steel pipe and use of tank for water distribution were independent risk factors.CONCLUSIONS Most of the investigated hospitals have high level contamination and high concentration of legionella spp.in Shanghai,which would likely to acquire legionellosis.Active surveillance of water distribution systems and nosocomial acquired legion Ella pneumonia should be conducted and disinfection of the water distribution system should be considered.