An ecologic study on Legionella in cooling tower water in some districts of Shanghai

Lin Hai-jiang,Hu Fu-yu,Wang Wei-bing,Jiang Wei-li,Xu Biao,Chen Yue
DOI: https://doi.org/10.3969/j.issn.1004-8685.2007.05.012
2007-01-01
Abstract:Objective:To learn the ecologic characters of Legionella in cooling tower water of central air-conditioning system and provide evidence and information for Legionella control.Methods:A study on relationship between temperature and the proliferation of Legionella in cooling tower water and the relationship between the biofilm formations and the proliferation of Legionella were carried out.Results:The quantity of Legionella in central air-conditioning system cooling tower water and bio-film had a significant association with temperature.The pollution status aggravated gradually with temperature rising and it reached its peak during July to September,and then began to drop gradually shortly afterwards,especially in summer and autumn.In cold winter and spring,however,Legionella could not be detected in the cooling tower water,but it could be detected in bio-film.Conclusion:The growth of Legionella in central air-conditioning system cooling tower water has seasonality and biofilm provide safe-room for Legionella to live through.
What problem does this paper attempt to address?