Microbial Contamination of Air-conditioning Ventilation System in Some Public Places in Minhang District of Shanghai

LIU Ji-qian,WANG Xiao-guang,SONG Chi-ping,LUO Ling-fei,WANG Ping,OUYANG Lin,ZHANG Ying-hua,YANG Li-hua
DOI: https://doi.org/10.13329/j.cnki.zyyjk.2011.13.009
2011-01-01
Abstract:[Objective]To understand the microbial contamination status of centralized air ventilation system in public places in Minhang district of Shanghai.[Methods]According to the Hygienic standard for centralized air ventilation system in public place(Ministry of Health,2006) and the Hygienic requirements for operation of air-conditioning ventilation system in public place(Shanghai local standard DB31/405-2008),the microbiological parameters of centralized air ventilation system in 4 public places of Minhang district were sampled and tested from July to Aug in 2010.[Results]Among 4 public places,the qualification rate of total bacteria count of air supply of centralized air ventilation system was 26.32%(5/19),and that of total fungi was 63.16%(12/19).The qualification rate of total bacteria count on the surface of air supply duct was 9.74%(18/19),and that of total fungi was 100%(19/19).The detection rate of legionella pneumophila in cooling water was 100%.[Conclusion]The microbial contamination was found in centralized air ventilation system in public places in Minhang district of Shanghai.It is necessary to reinforce the cleaning,disinfection and health inspection of centralized air ventilation system.