The Study Of The Effect Of Cleaning The Ventiducts Of The Central Air-Conditioning Systems On The Air Quality In The Waiting-Area Of Shanghai Subway Line 1

Yang Jun,Zhou Qi-Xing,Tan Ying-Xiang,Fu Chao-Wei
2007-01-01
Abstract:[Objective]To assess the role of cleaning the ventiducts of the central air-conditioning systems in the air quality in the waiting-area of Shanghai Subway Line 1. [Methods] The air sample was collected before and after cleaning the ventiducts of the central air-conditioning systems in the waiting-area of Shanghai Subway Line 1. The samples for total bacterial count (TBC) were collected by the plates with the natural sedimentation method and were sent to culture and test in the lab immediately. Carbon dioxide (CO2) and inhalable particles (IP) were recorded in the field. The sampling methods were with the sanitary-surveillance technic norm of the public place (GB/T 17220-1998). The pair t test was occupied for all data. [Results] In the waiting-area of Shanghai Subway Line 1, the average concentration of CO2 increased from 0.058% before the cleaning to 0.067% after that (t=-8.040, P=0.000), and the average of TBC from 4.960 to 6.630 CFU per plate(t=-5.515;P=0.000). [Conclusion]No evidence was found that cleaning the ventiducts of the central air-conditioning systems could improve the air quality in the waiting-area of Shanghai Subway Line 1.