Analysis on Environmental Quality in Shanghai Metro Stations

叶晓江,连之伟,蒋淳潇,陈焕新,刘陵飞
DOI: https://doi.org/10.3969/j.issn.1003-0344.2009.05.015
2009-01-01
Abstract:A field investigation was carried out in Shanghai Metro stations to study and analysis its indoor environmental quality.The result showed that the temperature and humidity condition in metro stations were good.The concentrations of HCHO and CO were less than the Chinese Indoor Air Quality Standard and that of CO2 were above the standard in some stations.The main problem in Shanghai Metro stations was the concentrations of particulate matters were at high levels.The mass concentrations of PM10 and PM2.5 were 372±209 μg/m3and 293±193 μg/m3,respectively.Reasonable ventilation design and metro shield gate could play a vital effect on improve the indoor environmental quality in metro stations.
What problem does this paper attempt to address?