Study on the large transformer protection principle based on the winding parameter identification

CHU Yun-long,HAO Zhi-guo,LI Peng
DOI: https://doi.org/10.3969/j.issn.1674-3415.2006.23.001
2006-01-01
Abstract:A transformer protection algorithm based on the winding parameter identification is described in this paper.First of all,the algorithm calculates the each side winding flux in equation which uses the transformer data(currents and voltage) and the transformer parameter including resistance and leakage inductance at each transformer terminal.In normal operation state,the magnetic flux is equal between the primary and secondary winding.But it is not equal in internal fault state,for the transformer structure and parameter has been changed.Then,the algorithms can discriminate fault status from failure free operation by estimating whether the flux of the primary and secondary winding is equal or not.The results indicate that the proposed algorithms can successfully detect the different styles internal fault,and can sensitively find the fault in a fraction of a cycle.The algorithm also remains stable during magnetizing inrush and over-excitation,and is not affected by changing the core characteristics.The project is supported by National Natural Science Foundation of China(No.50577050).
What problem does this paper attempt to address?