Analysis on Broken Conductor Load of Suspension Tower for UHVDC Power Transmission

ZHANG Zi-fu,MO Zeng-lu,HE You-xing,SHEN Guo-hui
DOI: https://doi.org/10.13335/j.1000-3673.pst.2010.05.004
2010-01-01
Abstract:The breakage of conductor/ground wire seriously affects the secure operation of transmission line. According to the features of UHVDC power transmission lines, the broken conductor model for bundled conductors of continuous span is built by finite element software ABAQUS, and through the simulation of conductor breakage happened in continuous spans the swing amplitude of V-shaped insulator strings, the impact load and the broken conductor load of phase conductors are obtained. Comparing the simulation results with those by theoretical calculation, it is known that the values of broken conductor load specified in the Chinese Design Codes are rational, and the tipping-over and collapse of suspension towers designed by the code can be prevented to a certain extent.