Research of impact effect on transmission line system due to sudden breakage of conductor

Guo-hui SHEN,Zeng-lu MO,Bing-nan SUN,Wen-juan LOU
DOI: https://doi.org/10.3969/j.issn.1000-3835.2009.12.002
2009-01-01
Abstract:The sudden breakage of conductor enables the quick release of tension in conductor,which causes the dynamic impact effect on transmission line system. However,the design codes of transmission towers usually consider conductor breakage load as static load. Taking a transmission line system as example,finite element method was employed to construct the tower-line model. In calculation,the cases of one sub-conductor breakage to six sub-conductors breakage were simulated and the impinging of dropping conductors against ground was considered. The conclusions show that the bigger the number of broken sub-conductors is or the closer the broken point is to the insulator,the larger the swing amplitudes and the peak axial forces on insulators of tangent towers will be. The breakage of conductors will result in two major impacts: the one is induced directly by the sudden breakage of conductors and the other is induced by impinging of dropping conductors against ground.
What problem does this paper attempt to address?