Faulty feeder selector based on traveling wave according to IEC61850 standard

SHI Shenxing,REN Li,LIU Zeyu,DONG Xinzhou
2011-01-01
Abstract:A faulty feeder selector based on traveling wave theory and IEC61850 standard is developed for the single-phase grounding fault of digital substation in non-solid grounding power system.Its principle is presented: the amplitude of initial traveling wave on faulty feeder is higher than those on other feeders and its polarity is in inverse.General model of faulty feeder selector is established according to IEC61850,which is a logic device with three logic nodes.Its hardware scheme and software flowchart are designed,including the wavelet-transform-based traveling wave algorithm and modulus-maximum-based criterion,and especially the communication unit conforming to the MMS of IEC61850.Its successful operation in a digital substation verifies its feasibility.
What problem does this paper attempt to address?