Self-healing of single-phase grounding fault for power distribution lines

SHI Shenxing,DONG Xinzhou,WU Jiahua,SHEN Dong
2012-01-01
Abstract:A self-healing scheme is presented for the single-phase grounding fault of distribution lines,which consists of four parts:fault detection,faulty feeder selection,faulty section identification and faulty feeder isolation.The fault detection is based on the open-delta-side voltages of PT.A single-phase grounding fault is identified when the measured voltage is greater than the setting value.The faulty feeder selection is based on the current traveling waves.The feeder with different traveling wave polarity is selected as the faulty one.The faulty section identification is based on the synthesized results of faulty feeder selection.After the faulty feeder is selected,close the interconnection switch at the load side first,then open its incoming switch and isolate the power source side of faulty.Simulative results show that the scheme realizes the automatic quick isolation of single-phase grounding fault without power loss of load.