Experimental Study on Superheat Phenomena of Two-phase Mechanically Pumped Cooling Loop

LIU Jie,PEI Nian-qiang,GUO Kai-hua,HE Zhen-hui
DOI: https://doi.org/10.3321/j.issn:0529-6579.2007.06.007
2007-01-01
Abstract:Mechanically pumped cooling loop is a kind of heat release equipment with two-phase work fluid circulating in the closed tube .From the tests results of the system startup, it is found that heat load will cause a superheat state and at the outlet of the evaporator with a pressure shake of the whole loop. In order to investigate the superheat phenomena of MPCL, tests have been carried out with different operation conditions such as set-point evaporative temperature, mass flow and heat load. It concluded that the less evaporative temperature is, the higher superheat temperature is. Moreover, superheat will last a shorter time with the heat load increasing.Finally, it is also pointed out that a greater mass flow will cause a larger pressure shake.
What problem does this paper attempt to address?