Dynamic Hysteresis Loss Model of Power Transformer under DC Current Biasing and Its Verification

曹林,何金良,张波
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.24.024
2008-01-01
Abstract:Under DC current biasing the additional losses of power transformer increase significantly, as a result the loss of iron core can not be identified from the no-load loss correctly. It is necessary to establish an accurate model of the iron core to evaluate its possible overheating problem. Based on the Jiles-Atherton model, the dynamic hysteresis loss model of the transformer core considering the classic eddy current loss and abnormal loss is developed, which is suitable for all the reasonable coefficient of reversible magnetization and adopting the flux density as entry variable. By using genetic algorithm, the model parameters are extracted from the no-load experimental results of a small single-phase transformer and then applied to simulate the iron core behavior at different magnitudes of DC biasing current. Compared with the experimental results of DC current biasing, the simulations are in a good agreement. This indicates that the dynamic hysteresis loss model can describe the relation between the magnitude of DC biasing current and transformer core loss correctly and practically.