Prediction of Core Loss in Transformer Laminated Core under DC Bias Based on Generalized Preisach Model

Yang Li,Jun Zou,Yongjian Li,Jianguo Zhu
DOI: https://doi.org/10.1109/tmag.2023.3298342
IF: 1.848
2024-01-01
IEEE Transactions on Magnetics
Abstract:DC transmission systems that operate in monopole-grounded return mode can cause DC magnetic bias in power transformers, leading to higher core losses, local overheating, early insulation fatigue, premature failure, and reduced service life of the transformer. Accurate prediction of core loss under DC bias remains a challenge. In this paper, a generalized Preisach hysteresis model is proposed to evaluate the core loss and its distribution in power transformers under DC bias. The generalized Preisach model incorporates reversible and irreversible magnetization components, and its Preisach distribution function and the reversible magnetization component are determined solely based on the M-H limiting loop. To verify the proposed model’s accuracy, a transformer laminated core prototype is developed and core losses under DC bias are predicted using the proposed model coupled with finite element method. The comparison between the prediction and experiment confirms good agreement.
What problem does this paper attempt to address?