Sub-Cooler for Air Conditioner Based on Thermoelectric Effect of Semiconductor

BAI Ze-yu,MEN Yi-fan,WANG Yu-chen,WEI Wei,CHEN Jiang-ping
DOI: https://doi.org/10.3969/j.issn.2095-4468.2012.03.102
2012-01-01
Abstract:The overall efficiency and total capacity of an air conditioning system are strongly influenced by degree of sub-cooling.A traditional method of increasing degree of sub-cooling is to enlarge the heating area of the condenser,which therefore leads to higher cost and larger size of the system.In this paper,two sub-coolers based on thermoelectric effect of semiconductor were designed and tested for comparison.The result shows that, with the designed sub-cooler working,the degree of sub-cooling at the exit of condenser increases by 1.5℃and the system's COP increases by 6.5%.