Some Problems on Inspection of Concrete Block Wall

Xiu-mu FANG,Zhong-liang ZHAO,Rui ZHANG
DOI: https://doi.org/10.3969/j.issn.1002-8528.2008.10.015
2008-01-01
Building Science
Abstract:Heat transfer coefficient of main body of wall is usually inspected by heat flow meter.In this paper,the condition of using heat flow meter was analyzed,and it was pointed out that it was unsuitable to inspect wall of non-uniform surface temperature distribution with heat flow meter,such as concrete block wall.And then,taking concrete block wall as an example,the temperature distributions of both internal and external surfaces under different outdoor temperatures were simulated.The simulation was under the following three conditions:with no insulation,external insulation and internal insulation.For the insulated walls,insulation thickness was changed gradually,so that the surface temperature and temperature difference of both sides were simulated.Thus the conclusion,heat flow meter should be put on the insulated side was drawn.Furthermore,the simulation results indicated that when the outdoor temperature was above 0 ℃,for internal wall with more than 70 mm insulation,it was also feasible to put heat flow meter on the non-insulated side.