Study on the Selection of UHV AC 1000 Kv Insulator Type

SU Zhi-yi,ZHOU Jun,LI Wu-feng,XU Yue-neng
DOI: https://doi.org/10.3969/j.issn.1004-9649.2006.10.004
2006-01-01
Abstract:In order to select insulator type for the UHV 1 000 kV lines, the artificial contamination tests were carried out for different types of insulator under different pressure and in different typical kinds of equivalent salt deposit density(ESDD). The test shows that the flashover voltage of polluted insulators regularly decreases with the increasing of the altitude. And there are certain relationships between voltage and the shed shape. At last, the suggestions on insulator type selection for UHV AC 1 000 kV transmission lines are put forward. In the low and moderate contamination area, tri-shed insulator is firstly being recommended, and in the low contamination area, double-shed insulator is also being recommended. The moderate and above contamination area, composite insulator are recommended to use. However the normal type 300 kN insulator is not being recommended in the UHV transmission line.