Research on Impact of Series Resonant FCL on Subsynchronous Resonance

SUN Wen,ZHANG Xiaotian,HU Yongrui,XU Zheng
DOI: https://doi.org/10.3969/j.issn.1007-290X.2012.05.007
2012-01-01
Abstract:The paper introduces structure and principle of series resonant fault current limiter as well as mechanism of subsynchronous resonance.The paper takes data of maximum operating mode in high-water period,minimum operating mode in high-water period and maximum operating mode in low-water period of Guangdong power grid in 2015 as subject investigated and it analyzes impact of mounting series resonant FCL in transmission lines of power plant upon subsynchronous resonance of generating units by using state space analysis method.Characteristic value within subsynchronous frequency of the system is calculated;furthermore,system stability is also analyzed.The result shows that series resonant FCL can lead to subsynchronous resonance,attention to which should be paid in technical application.
What problem does this paper attempt to address?