Analysis and Optimization of Axial Magnetic Field Characteristics of 252 Kv Vacuum Interrupter Contacts

刘志远,郑跃胜,王仲奕,王季梅,荣命哲
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.15.021
2008-01-01
Abstract:Contacts of vacuum interrupters have important influence on nominal current carrying capability and short circuit current interrupting capacity of vacuum circuit breakers. By using 3D finite element method, axial magnetic field (AMF) characteristics of single coil contacts used in 252 kV vacuum interrupters were analyzed with single factor analysis and orthogonal regression analysis. The analyzed AMF characteristics include axial magnetic flux density at current peak, axial magnetic flux density at current zero, and conductor resistance. Regression equations that link AMF characteristics and contact parameters were given. Contact parameters that have significant influence on AMF characteristics were shown. Ideal AMF characteristics should be as follows: strong axial magnetic flux density at current peak, weak axial magnetic flux density at current zero and low conductor resistance. It is shown that the ideal AMF characteristics can be achieved by combination of optimization based on design of experiment, finite element method, and statistical analysis. By this way optimal contact parameters are found for a 252 kV AMF contact.
What problem does this paper attempt to address?