Electric Field Distribution of EHV and UHV Transmission Lines Erected in Common Corridor and Research on Corridor Optimization

Shi Chaoqun,Zhu Jun,Wu Jingwen
DOI: https://doi.org/10.3969/j.issn.1003-6954.2013.04.001
2013-01-01
Abstract:The number of conductor with different voltage level is more complicated than single circuit when EHV and UHV transmission lines are erected in the common corridor,so there are many factors which will influence the distribution of electric field.The calculation model of power-frequency electric field is established based on charge equivalent method in order to analyze the distribution of electric field when using the common corridor,and Matlab is utilized to develop simulation program for the visible analysis of electric field distribution under the transmission lines at 1.5 m above the ground.The discussion lays emphasis upon some influencing factors to the distribution of electric field in the transmission corridor,such as the phase sequence of EHV and UHV transmission lines,the approaching distance between EHV and UHV transmission lines,and the clearance of conductor to the ground.Research shows that the phase sequence and the clearance of conductor to the ground have a great influence on the maximum of electric field,and there is a linear growth relationship between high-intensity coverage area of electric field and the approaching distance.Finally,the suggested phase sequence,approaching distance and clearance of conductor to the ground when EHV and UHV transmission lines are erected in the common corridor are proposed according to the criterion of electromagnetic environmental evaluation.
What problem does this paper attempt to address?