Analysis of Configuration and Corridor Width of HVAC and HVDC Transmission Lines on Same Tower

LI Benliang,QIAO Ji,ZOU Jun,YUAN Jiansheng
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.1151
2017-01-01
Abstract:Hybrid electric field of ac/dc transmission lines on the same tower is a most important factor for line configuration design. Lateral profile of electric field on ground has close relationship with superposition and distribution of ac and dc component. In this paper, hybrid electric field and ion current are calculated and analyzed for double-circuit 330kV or 750kV ac lines and?1100kV dc lines on the same tower with different configuration and phase sequences. Minimum conductor heights and corridor widths are also computed. Results show that electric field profile on ground level can be categorized into three regions: ac, hybrid and dc. ‘Inverted triangle’ and ‘vertical’ structures are proposed to be used to separate positions of peak values of dc and ac components. Corridor widths are determined by ac field for 750kV lines while by both ac and dc fields for 330kV ac lines. Finally, configurations I (phase sequences 6) and II (phase sequences 4) are proposed for hybrid ac/dc lines on the same tower.
What problem does this paper attempt to address?