Study on the start time of mechanical exhaust system in economical building

GUO Zeng-hui,HE Qi-ze,LI Chang-hai
DOI: https://doi.org/10.3969/j.issn.1009-0029.2013.06.022
2013-01-01
Fire Science and Technology
Abstract:Through experimental research,the fire detecting time of heat detector and smoke detector with different distances to the fire source were measured.By literature research and theoretical analysis,the model of heat detector and smoke detector’s detecting time were gotten.The start time of mechanical exhaust system was analyzed.Results showed that the detecting time increases with the distance between the detector and fire source increases,and the structural beams can slow the pro-phase temperature raise of the smoke near the ceiling.The calculation result is bigger than the experimental result.The detecting time of smoke detector is shorter than that of heat detector.Generally the start time of mechanical exhaust system in building lower than 6 m won’t exceed 180 s.
What problem does this paper attempt to address?