Influence of improving medium-speed pulverizer outlet temperature on the operation of boiler

LI Wen-hua,YANG Jian-guo,CUI Fu-xing,FENG Guo-hua,ZHAO Hong,ZHANG Qin,TONG Hong-zheng,LIN Min-cheng
DOI: https://doi.org/10.3969/j.issn.1004-9649.2010.10.007
2010-01-01
Abstract:Fudong 24 was analyzed in atmosphere by using the TG-FTIR,CO began to emit at 265 ℃,and there were only H2O & CO2 emitted when it is lower than 265 ℃.Also by thermal equilibrium calculation of pulverizer,it could be ensured that the coal milling system was safe when the input air temperature of medium-speed pulverizer is lower than 265 ℃.Based on the feasibility study,the pulverizer outlet temperature of a 300 MW boiler was increased from 75 ℃ to 95 ℃.The pulverizer input air temperature was increased to 261.4 ℃.No CO was detected in outlet flow of the pulverizer.The primary air temperature and the secondary air temperature of the boiler decreased a little.The combustion inside the furnace and other parameters of the boiler were affected obscurely.The flue gas temperature decreased 7 ℃,furthermore the boiler efficiency increased 0.37%,and the standard coal consumption in generation decreased 1.17 g/(kw.h).