Experimental Study on Micronized Coal Reburning for a 200MW Coal-fired Boiler

SI Dong-bo,CHI Zuo-he,HUANG Yu-ming,YING Ming-liang,LI Jian,LI Feng-rui,FANG Lei,CAI Shang-qi,QI Liang
DOI: https://doi.org/10.3321/j.issn:0258-8013.2007.26.001
2007-01-01
Abstract:A 200MW tangentially coal-fired boiler was retrofitted with a micronized coal reburning system and the performance tests were conducted subsequently. Ultrafine pulverized-coal contained in the tertiary air was used as the reburning fuel and the oxygen level of the tertiary air was reduced with the use of flue gas recirculation(FGR). The effects of OFA velocity, pulverizing system operating mode, and FGR on the NOx emissions were investigated during the tests. The NOx reduction performance of this reburning system was also evaluated when increasing the ultrafine pulverized-coal content in the tertiary air. The test results show that NOx emissions can be reduced by approximately 40% under the optimal operating condition, with no significant impact on boiler performance. And only a 1.4% increase in fly ash carbon content is observed under this condition.