Experimental Study of Single-pane Fire-resistant Glass Performance with Sprinkler Protection

Shu Xueming,Shao Quan,Su Guofeng,Chen Tao,Yang Rui,Shen Shifei,Yuan Hongyong
DOI: https://doi.org/10.3969/j.issn.1009-1742.2006.06.012
2006-01-01
Engineering Science
Abstract:On account of fine appearance and lucidity of glass, fire-resistant glass has been widely used as architecture exterior materials and fire-resistant compartmentation in modern buildings.Especially,single-pane fire-resistant glass is more widely used than compounding one because of its higher light transmission and less weight in construction.However,single-pane fire-resistant glass can only prevent the spread of fire and smoke,while high temperature and thermal radiation flux on its rear surface may cause a new fire on the protected side.Furthermore,fire-resistant glass is usually quite close to evacuation passage,so it will be harmful to security evacuation.These shortcomings prevent single-pane fire-resistant glass from using in practice.This article describes the experimental study of single-pane fire-resistant glass performance with sprinkler protection.The test setup was introduced in detail,and the test results were discussed.It is showed that the temperature and thermal radiation flux on the protection side of single-pane fire-resistant glass with sprinkler protection are quite lower than those without sprinkler condition.The fast responding sprinkler can automatically spray well-proportioned water and protect certain area.The study of this article may be of benefit to the evacuation calculation in performance-based fire design and engineering application of fire-resistant glass.
What problem does this paper attempt to address?