Experimental study of pool fire suppression by water mist in enclosure

Hua Zhou,Dong Deng,YANG Hua-yong
2007-01-01
Abstract:A series of Class-B pool fire suppression tests were carried out to find out the effect of water mist fire suppression in different conditions. A novel water mist spray-head was developed and its spray characters were measured. The layout of fire test enclosure and the test procedure were introduced. Seventeen fire tests were done to investigate the influencing factors on fire suppression effect, such as the radial distance of pool fire to spray-head, fire power, spray-head height, fire shield and spray pressure. The temperature fields of the processes of fire tests were measured and contrasted. Experimental results show that the shield condition of fire, spray pressure and fire power have important effects on water mist fire suppression. For this spray-head, 10-12 MPa spray pressure is recommended. 2B and higher-power fires are easy to be put out, but IB and smaller-power fires are difficult to be distingushed by using this spray-head. Gasification and suffocation of water mist play critical roles in the process of pool fire suppression by water mist.
What problem does this paper attempt to address?