Measurement of Atomization Characteristics on Water Mist Fire Suppression Nozzle

FAN Ming-hao,ZHOU Hua,ZHU Chang,YANG Hua-yong
DOI: https://doi.org/10.3785/j.issn.1008-973x.2005.09.033
2005-01-01
Abstract:For better atomization effect and helping understanding of the atomization process, a direct-jet nozzle for fire suppression was improved by introducing a swirl chamber, and the spray characteristics were investigated. The primitive atomization mechanism was discussed, and the system parameters, measurement principles and measurement process of 3D phase doppler particle anemometer (PDPA) were presented. Different pressures were applied to the nozzle, and the spray cone angles with and without the swirl chamber were measured. With the spray pressure was 2. 5 MPa, the sauter mean diameter (SMD), the axial, radial and tangential velocities were measured, and the experimental data on the location of spray axial center were compared with those on the location of spray external edge. The results show that the nozzle with swirl chamber has larger spray cone angle and better atomization effect compared with the nozzle without one, and that the nozzle's atomization process agrees with the stability theory. The spray characteristics have remarkable influence on the spray axial center and on the spray external edge.
What problem does this paper attempt to address?